Division 7 Ebook Page 428 FOAMULAR Insulation, New Roof, Below Membrane, 07 22 16

FOAMULAR , Thermal, Tapered Roof Insulation D. Insulation joints shall not exceed 1/4" in width. Joints wider than 1/4" shall be filled with the same insulation. E. Insulation shall be field trimmed to fit tightly around roof protrusions and terminations. F. Apply only as much Tapered [THERMAPINK, FOAMULAR] and fill roof insulation as can be covered by the roofing membrane on the same day. Apply roof insulation in parallel rows with end joints staggered. Install side and end joints closely but do not force together. In a two layer application, apply second layer panels parallel to the first layer but with side and end joints staggered in relation to the first layer. G. Place the [THERMAPINK, FOAMULAR] board with the printed logo surface down so that the black lettering is not exposed to potential solar heat gain. H. [For ballasted roofing systems (including PRMA*) with no cover board over the XPS,] black/dark (non- white) roofing membranes (or filtration fabrics in PRMA) over THERMAPINK and FOAMULAR insulation shall be ballasted immediately after placement to prevent potential heat damage from sun exposure and wind displacement of the insulation under the membrane/fabric. I. [For mechanically attached and fully adhered roofing systems,] in areas where black/dark membranes are used and where "reflected solar energy" is expected to be present, THERMAPINK and FOAMULAR insulation need protection in addition to normally specified cover boards. For example, roof areas adjacent to higher walls, particularly walls with reflective surfaces, or near large rooftop HVAC units, or near or in between clusters of mechanical equipment, or near other structures with reflective cladding (metal or glass); or near higher reflective parapets, all such areas should be considered for additional heat protection. Such roof areas must be covered with pavers or ballast. Black/dark (non-white) membranes must be coated with white reflective topping, and maintained white, to avoid damage due to the intensified heat exposure from reflected sun in such areas. J. Insulation shall be [loosely placed, secured] in accordance with membrane manufacturer's requirements. The insulation below the membrane is to be held in place with [ballast, compatible adhesives, mechanical fasteners in conjunction with the overlayment and/or membrane system]. [Mechanical fasteners shall be of sufficient number and adequate pattern to resist displacement of insulation by wind uplift forces.] When adhering or exposing Tapered/fill THERMAPINK or FOAMULAR insulation to hot bitumen, the bitumen must be allowed to cool to between 200F and 250F. 3.1.1.5 OVERLAYMENT A. Only dry overlayment materials shall be used. If overlayment materials become wet, allow them to fully dry before proceeding with roofing application. Requirements for overlayment materials and thickness may vary. Contact membrane manufacturer for their individual requirements. B. [Rigid overlayment shall be [mechanically attached, adhered with a suitable adhesive] per manufacturer's recommendations.] Mechanical fastening of insulation and rigid overlayment may coincide so that fastener penetrates overlayment and THERMAPINK or FOAMULAR into the structural substrate the minimum distance prescribed for adequate wind uplift resistance by the fastener manufacturer. [Loose lay flexible sheet overlayment over Tapered [THERMAPINK, FOAMULAR] and cover with a membrane attached per the manufacturer's recommendations. Edges and ends of rolls shall be lapped a minimum of 6".] C. When cleaning agents and seam adhesives used are solvent based and capable of causing cavitation of the underlying [THERMAPINK, FOAMULAR] insulation, use care when preparing membrane edges for in-field seam splicing. ROOF BOARD INSULATION 07 22 16 - 6

Previous Page
Next Page