Division 7 Ebook Page 399 EcoTouch FIBERGLAS Insulation, 07 21 16

Fiberglas, Exterior Wall Thermal Insulation D. Insulation, at Metal Framing: Note to Specifier: Select from the following table: Thickness Width Length R-value (per ASTM C518) 3"89mm 16" 406mm - 24" 609mm 96" 2438mm 11.0 3"89mm 16" 406mm - 24" 609mm 96" 2438mm 13.0 6"159m m 16" 406mm - 24" 609mm 96" 2438mm 19.0 E. Insulation, at Wood Framing: Note to Specifier: Select from the following table: Thickness Width Length R- value (per ASTM C518) 3"89mm 15" 381mm - 23" 584mm 93" 2362mm 11.0 3"89mm 15" 381mm - 23" 584mm 93" 2362mm 13.0 3"89mm 15" 381mm - 23" 584mm 93" 2362mm 15.0 6"159m m 15" 381mm - 23" 584mm 93" 2362mm 19.0 5"139m m 15" 381mm - 23" 584mm 93" 2362mm 21.0 F. Vapor Retarder Perm Rating: ASTM E 96. 1. Foil Facing: 0.50 max. perms. 2. Kraft Facing: 1.00 max. perms. G. Surface Burning Characteristics: ASTM E 84. 1. Unfaced Insulation: Maximum flame spread: 10, Maximum smoke developed: 10 2. Foil Faced Insulation: Maximum flame spread: 75, Maximum smoke developed: 150 3. Kraft-Faced Insulation: Maximum flame spread: Not Rated Maximum smoke Developed: Not Rated Note to Specifier:Kraft and standard foil facings on this insulation will burn and must not be left exposed. The facing must be installed in substantial contact with the unexposed surface of the ceiling, wall or floor finish. Protect facing from any open flame or heat source. H. Combustion Characteristics: Unfaced insulation passes ASTM E 136 test. I. Dimensional Stability: Linear shrinkage less than 0.1% 2.1.1.6 MISCELLANEOUS MATERIALS A. Provide materials, not specifically described but required for a complete and proper installation of the work in this section. THERMAL BLANKET INSULATION 07 21 16 - 6