Division 7 Ebook Page 396 EcoTouch FIBERGLAS Insulation, 07 21 16

Fiberglas, Exterior Wall Thermal Insulation E. Dimensional Stability: Linear shrinkage less than 0.1%. 2.1.1.3 THERMAL INSULATION (700 SERIES) A. Type 701: Unfaced glass fiber thermal insulation complying with ASTM C 553, Type III and ASTM C 665, Type I. B. Type 711: Unfaced glass fiber thermal insulation complying with ASTM C 553, Type III and ASTM C 665, Type I. C. Type 703: Unfaced, FRK (foil) faced and ASJ (white) faced glass fiber thermal insulation complying with ASTM C 612, Type 1A and 1B. D. Type 705: Unfaced, FRK faced and ASJ faced glass fiber thermal insulation complying with ASTM C 612, Type 1A and 1B. Note to Specifier: Select from the following table: Thickness Width Length R-value Type 701 1" 25mm 24" 609mm 48" 1219mm 4.2 1" 38mm 24" 609mm 48" 1219mm 6.3 2" 51mm 24" 609mm 48" 1219mm 8.3 2" 64mm 24" 609mm 48" 1219mm 10.4 3" 76mm 24" 609mm 48" 1219mm 12.5 3" 89mm 24" 609mm 48" 1219mm 14.6 4" 102mm 24" 609mm 48" 1219mm 16.7 1" 25mm 24" 609mm 48" 1219mm 4.0 1" 38mm 24" 609mm 48" 1219mm 6.0 Type 711 2" 51mm 24" 609mm 48" 1219mm 8.0 2" 64mm 24" 609mm 48" 1219mm 10.0 3" 76mm 24" 609mm 48" 1219mm 12.0 4" 102mm 24" 609mm 48" 1219mm 16.0 Type 703 1" 25mm 24" 609mm 48" 1219mm 4.3 1" 38mm 24" 609mm 48" 1219mm 6.5 2" 51mm 24" 609mm 48" 1219mm 8.7 2" 64mm 24" 609mm 48" 1219mm 10.9 Type 705 3" 76mm 24" 609mm 48" 1219mm 13.0 3" 89mm 24" 609mm 48" 1219mm 15.2 4" 102mm 24" 609mm 48" 1219mm 17.4 E. Vapor Retarder Perm Rating: ASTM C 1136. 1. FRK (foil) facing Perms Maximum 0.02 2. ASJ (white) facing Perms Maximum 0.02 F. Surface Burning Characteristics: ASTM E 84. Note to Specifier: Select from the following table: THERMAL BLANKET INSULATION 07 21 16 - 3