Division 22 23 Ebook Page 46 Pipe & Mechanical Insulation Brochure

16 Thermal conductivity Mean Temperature F k* Mean Temperature C * 50 0.26 10 0.037 75 0.27 25 0.040 100 0.29 50 0.045 150 0.33 75 0.050 200 0.38 100 0.056 250 0.43 125 0.063 300 0.49 150 0.070 350 0.55 175 0.078 Conductivity Btu in/hr ft. 2 F 50 100 150 200 75 250 300 350 Mean Temperature, F 0.2 0.3 0.4 0.5 0.6 * k = Btu in/hr ft 2 F; = W/m C Apparent thermal conductivity data determined in accordance with ASTM Practice C1045 with data obtained by ASTM Test Method C335. Values are nominal, subject to normal testing and manufacturing tolerances. Installation instructions 1. Measure the length of insulation required according to the fabrication guide located on the carton. 2. Cut completely through the insulation and jacket. Use a flap tool to fillet a stapling flange on one end of the insulation. 3. Each section of insulation may be secured around the pipe using either outward-clenching staples and mastic or outward-clenching staples and pressure- sensitive, vapor-retarder tape. 4. Adjacent sections must be tightly butted together and then sealed with vapor-retarder tape. Additional installation instructions Special care must be taken to vapor-seal systems operating below ambient temperatures. If indoor applications will be painted, use only a water-based latex paint. Outdoor applications require protection from weather. 1. The standard used to determine surface burning characteristics measures and describes the properties of materials, products or assemblies in response to heat and flame under controlled laboratory conditions and should not be used to describe or appraise the fire hazard or fire risk of materials, products or assemblies under actual fire conditions. However, results of this test may be used as elements of a fire risk assessment, which takes into account all of the factors that are pertinent to an assessment of the fire hazard of a particular end use. Values are reported to the nearest 5 rating. Physical property data Property Value Test Method Pipe/equipment Operating Temperature (single-layer application) 0F to 650F (-18C to 343C) ASTM C411 Insulation Jacket Temperature Limitation -20F to 150F (-29C to 66C) ASTM C1136 Jacket Permeance 0.02 perm ASTM E96, Proc. A Minimum Burst Strength 100 psi ASTM D774/D774M Compressive Strength at 10% Deformation 125 lb./ft 2 (5985 Pa) min. ASTM C165 Surface Burning Characteristics 1 Flame Spread: 25 Smoke Developed: 50 ASTM E84 FIBERGLAS Pipe and Tank Insulation

Previous Page
Next Page